Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2002 |
MECHANICAL - FINAL |
|
Approved |
OK FOR C OF O. |
| 01/03/2002 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) STAT WIRE NOT APPROVED FOR OUTDOOR USE. 2.) PAINT EXPOSED PVC W/LATEX PAINT. 3.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT SMALLER THAN 2". 4.) PROVIDE SCREEN FOR COMBUSTION AIR VENTS IN DOORS. RECALL FOR FINAL. |