Permit: T01CM03708

Parcel: 122131000

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/08/2002 MECHANICAL - FINAL Approved OK FOR C OF O.
01/03/2002 MECHANICAL - FINAL Denied IVRS - Inspection 0999*1.) STAT WIRE NOT APPROVED FOR OUTDOOR USE. 2.) PAINT EXPOSED PVC W/LATEX PAINT. 3.) YOU CANNOT TERMINATE CONDENSATE INTO A WASTE VENT SMALLER THAN 2". 4.) PROVIDE SCREEN FOR COMBUSTION AIR VENTS IN DOORS. RECALL FOR FINAL.