Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03707
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
10/09/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES: ART. 370-17 N.E.C. 1. CABLE TO BE SECURLY FASTENED AT BOXES, APPLIES TO MULTI GANG BOXES, REPLACE BOXES WITH TABS BROKEN OUT OR BENT OUT AS TO NOT SECURE CABLE. EXCEPTION IS FOR SINGLE GANG BOXES ONLY ( PLASTIC) | |
10/07/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) STRAP NM CABLE WITH IN 12" OF BOXES 2.) NEED CABLE CLAMP IN BOXES 2 GANG AND LARGER 3.) BACK TO BACK INSTALLATION IN A FIRE WALL. 4.) SUPPORT NM & SE CABLES AT PANELS & SERVICE 5.) BE CAREFULL OF NM CABLES & DATA AT RAFTER CUPS. |