Permit: T01CM03707

Parcel: 122131000

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM03707

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/10/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
10/09/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*NOTES: ART. 370-17 N.E.C. 1. CABLE TO BE SECURLY FASTENED AT BOXES, APPLIES TO MULTI GANG BOXES, REPLACE BOXES WITH TABS BROKEN OUT OR BENT OUT AS TO NOT SECURE CABLE. EXCEPTION IS FOR SINGLE GANG BOXES ONLY ( PLASTIC)
10/07/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) STRAP NM CABLE WITH IN 12" OF BOXES 2.) NEED CABLE CLAMP IN BOXES 2 GANG AND LARGER 3.) BACK TO BACK INSTALLATION IN A FIRE WALL. 4.) SUPPORT NM & SE CABLES AT PANELS & SERVICE 5.) BE CAREFULL OF NM CABLES & DATA AT RAFTER CUPS.