Permit: T01CM03664

Parcel: 12810078A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T01CM03664

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000*/ 1) STILL NEED TO SEE DUCT SMOKE DETECTORS IN RETURN PLENIUMS, FIRE/SMOKE DAMPERS INSTALLED. WILL CHECK ON FINAL
09/26/2001 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*NEED TO SEE OPENING PRIOR TO INSTALLING FIRE DAMPERS. PROVIDE INSTALLATION INSTRUCTION FOR VAV. BOXES FINISH INSULATING DUCTS & INSTALL TRANSITIONS.