Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM03664
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2001 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
10/09/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) REMOVE TILES AT EVERY SUPPORT POINT. 2.) TOO MANY SEISMIC WIRES MISSING 3.) SUPPORT MC CABLE FROM STRUCTURAL CIELING DO NOT SUPPORT FROM OTHER CONDUIT. | |
10/08/2001 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) REMOVE CIELING TILES AT EACH END OF FIXTURES FOR INSPECTION OF ALL FIXTURES 2.) REVISE PLANS TO REFLECT THE ADDITION OF FUSE BLOCKS TO FAN POWER BOXES AND THE ELIMINATION. OF THE SERVICE DISCONNECTS. 3.) LEAVE J BOXES AND OTHER POINTS OF TERMINATIONS FOR INSPECTIONS. |