Permit: T01CM03659

Parcel: 108213260

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T01CM03659

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/24/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*REVISED PLAN ON JOB.
10/22/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) ARE ALL CORRECTION LISTED 10/15/01 MADE? 2.) NO HANGER ON HORIZONTAL SINK DRAIN DID YOU COVER UPSTAIRS BEFORE APPROVAL? 3.) NO JOB SUPER AVAILABLE.
10/17/2001 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*PLEASE PROVIDE APPROVED REVISED PLAN.
10/15/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) SUPPORT COPPER VERTICAL TO SINK. 2.) ADD A UNION ON XPANSION TANK 3.) HARD PIPE T & P DRAIN WITH UNION. 4.) REDUCING PAN DRAIN FROM 1" TO 3/4" CONSIDERED AN OBSTRUCTION. 5.) 2" ABS HORIZONTAL TO SINK NEEDS HANGER 6.) REPAIR COUPLINGS ON NEW WORK NOT ACCEPTABLE.
10/10/2001 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*TEST ON ABS OK TEST ON COPPER OK PLEASE PROVIDE APPROVED REVISED DRAWING ON LOCATION OF WATER.
10/09/2001 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*CALL AGAIN.
09/27/2001 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*1ST FLOOR ROUGH ONLY TEST OK OK TO BACKFILL.