Permit: T01CM03650

Parcel: 14027063A


Addresses:

6351 S TUCSON BL

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/11/2002 PLUMBING - ROUGH, SOIL Approved CORRECTION MADE OK 2.) OK TO COVER.
09/05/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*DO NOT COVER! 1.) I REVIEWED THE DELTA ONE REVISION ABS IS INSTALLED SOMEWHAT LIKE THE PLAN, BUT DID YOU MISS THE SIZE AND LOCATION OF THE WATER LINE? ALSO, SOMEONE HAND WROTE A NOTE ABOUT SEPARATING SEWER AND WATER AT ALL POINTS. 2.)NOT INSTALLED PER PLAN 3.) PLEASE PROVIDE A LIST OF LICENSED SUBCONTRACTOR BEFORE NEXT INSP. INSPECTION.
08/29/2002 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*PLEASE READ 103,5.4.2 94 UPC RESPONSIBILTY OF CONTRACTOR TO INSURE WORK IS READY FOR INSPECTION BEFORE CALLING IT IN. FAILURE TO DO SO COULD RESULT IN A REINSPECTION FEE. 2.) IT MIGHT BE HELPFUL IF THE CONTRACTOR READ THE INSPECTORS NOTES AND COMPLY WITH ALL CORRECTIONS NOT INSTALLED PER PLAN A THREADED FITTING MAY NOT BE INSTALLED BELOW GRADE ON ITS BACK BLAKE TEE. EXPOSE TRANISITION FITTING ABS XPVC SUPPLY LISTING FOR UNDERGROUND COPPER DO NOT COVER.
08/28/2002 PLUMBING - ROUGH, SOIL Not ready for Inspection
08/27/2002 PLUMBING - ROUGH, SOIL Not ready for Inspection WATER TEST DOWN 2.) A BLAKE TEE MAY NOT BE INSTALLED BELOW GRADE OR ON ITS BACK. 3.) NEED TO SEE TRANSITION FITTING BETWEEN ABS AND PVC 4.) NOT INSTALLED PER PLAN 5.) DO NOT COVER 6.) UNDERSLAB COPPER TO BE TYPE "K"