Permit: T01CM03632

Parcel: 113074280

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/12/2002 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/11/2002 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) A/C DISCONNECT NOT COMPLETE 2) CLEANOUT EAST WALL NOT PLUGED 3) PENSULA MISSING OUTLET 4) CAULK F/P GAS LINE
02/07/2002 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) #12 WIRE NOT CONNECTED TO BREAKER IN PANEL ? 2) WIRING SIZE FUSES IN DISCONNECT REAR A.C. 3) DISCONNECT IS LOOSE 4) MISSING CLEANOUT, CAP EAST WALL 5) LOOSE OUTLET IN HALLWAY 6) CIRCUIT IN SERVICE PANEL 30 AMP LABELED RANGE ? 7) POWER OFF AT KITCHEN GFCI CANNOT CHECK GFCI'S 8) NO POWER AT WAHSER OUTLET 9) RECESSED CAN LIGHT TO CLOSE TO SHELF (LARGE CLOSET BEDROOM 10) NEED HOUSE ADDRESS NUMBER 11) CAULK FIREPLACE GAS LINE