Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 07/29/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE CORRECLTY IDENTIFY CONDUCTOR COLORS AT AND BREAKERS. |
| 07/26/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NOTES 1.) COMPLETE ITEMS ON ROOF PER WRITE UP 7/23/02 EACH BLD. OK TO CLEAR TEMP POWER TO TEST BLD #1 UNITS #1101,1102,1103 |
| 07/23/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* OK TEMP POWER FOR TEST SUBJECT TO BOND. 1.) PLEASE INSTALL A BLANK COVER ON JUNCTION BOX IN LAUNDRY. 2.) THE PANEL NEEDS PERMANENT LABELING OF BREAKERS 3.) AN APPROVED CONNECTOR IS NEEDED 1/4" INTO BOX TO PROTECT CONDUCTORS 4.) FINISH CONNECTIONS AND WIRING OF FIRE BELL EXPOSED CONDUCTORS ROOF. 5.) USE AN APPROVED CONNECTOR FOR DISCONNECT. 6.) PLEASE SECURE DISCONNECT TO WALL. 7.) SUPPORT SEALTITE WITHIN 12" OF BOX/DISCONNECT AND OFF OF ROOF. 8.) MAINTAIN WORKING CLEARENCE AT A/C DISCONNECT 9.) WE HAVE A WORKING CLEARENCE VIOATION FOR SUBPANEL PLEASE MAINTAIN 30" WITHIN X 36" INFRONT. 10.) GROUNDING ELECTRODE CONDUCTOR TO BE CONNECTED TO GROUNDED CONDUCTORS. |