Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T01CM03619
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/24/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL. | |
07/22/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) PLEASE LABEL BREAKERS 2.) A DISCONNECTING MEANS IS NEEDED FOR WATER HEATER 3.) DRYWALL SCREWS CAN NOT BE USED FOR GROUNDING 250-8 LIGHTING CONTACTOR. 4.) CLEAN SURFACE UNDER GROUND BAR 250-12. 5.) A SUPPORT STRAP WILL BE NEEDED FOR COOK TOP CABLE. |