Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/10/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 07/25/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
1) EXPOSE UNDERGROUND CONDUIT TO VERIFY DEPTH IN ONE LOCATION 2) ELECTRIC NOT COMPLETE, OUTLETS NOT PER PLAN BUILD TO PLAN OR REVISE PLAN TO ASBUILT AND HAVE CITY OF TUCSON APPROVAL 3) YOU MUST PROVIDE A SEPARATE GROUNDING SYSTEM FOR GARAGE, INSTALL 2 EACH 8' GROUND RODS AT LEAST 6' APART CONNECTED TO ELECTRIC SUB PANEL WITH A CONTINOUS #4 COPPER CONDUCTOR (NO SPLICES) 4) GROUND ALL METAL ELECTRIC BOXES 5) ALL LIGHT SWITCHES MUST BE GROUNDED |