Permit: T01CM03603

Parcel: 112044000

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/10/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
07/25/2001 ELECTRIC - INTERMEDIATE Denied 1) EXPOSE UNDERGROUND CONDUIT TO VERIFY DEPTH IN ONE LOCATION 2) ELECTRIC NOT COMPLETE, OUTLETS NOT PER PLAN BUILD TO PLAN OR REVISE PLAN TO ASBUILT AND HAVE CITY OF TUCSON APPROVAL 3) YOU MUST PROVIDE A SEPARATE GROUNDING SYSTEM FOR GARAGE, INSTALL 2 EACH 8' GROUND RODS AT LEAST 6' APART CONNECTED TO ELECTRIC SUB PANEL WITH A CONTINOUS #4 COPPER CONDUCTOR (NO SPLICES) 4) GROUND ALL METAL ELECTRIC BOXES 5) ALL LIGHT SWITCHES MUST BE GROUNDED