Permit: T01CM03599

Parcel: 124160190


Addresses:

1250 S EUCLID AV


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T01CM03599

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
03/26/2002 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection 0000*SIGN OFF SHEET SUBMITTED BOND POSTED
03/25/2002 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection 0245*NOTES 1.) STEEL CONDUIT FOR WATER BOND WIRE MUST HAVE BOND BUSHING AT ONE END OF CONDUIT TO BOND CONDUIT TO WATER BOND. 250-92 NEC. AND 3/4" FOR UFER. 2.) BOND BUSHING REQUIRED ON 4" CONDUIT ENTERING CT CAN AND IN GUTTER 2 1/2" NIPPLE, 3/4" CONNECTORS. PER 250-94 NEC. 3.) HI LEG FOR 3 0 DELTA SYSTEM TO BE ON B 0 BEYOND METERING PER #9287 CITY OF TUCSON ORDIN. CHANGE BLUE TO RED. 4.) INSTALL 2 GROUND ROD 6' MIN APART PER 250 NEC.