Permit: T01CM03581

Parcel: 125150190

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T01CM03581

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2002 FRAMING Approved IVRS - Inspection 0000*
05/30/2002 FRAMING Denied IVRS - Inspection 0999*/ 1) INTERIOR POST FOOTING NOT PER PLANS 3-#4 REBAR INSTALLED 4 REQUIRED 2) SUPPLY AND MECHANICAL RETURN AIR RESTRICTED TO TIGHT OF BENDS 3) FIRE BLOCK ALL FURRED OUT WALLS AND CEILING LINES AND DROP CEILING 4) WHAT IS DOUBLE 2 X 12 BEAM IN BEDROOM TO BEAR ON PROVIDE DETAIL 5) BLOCK ALL MECHANICAL DEFUSER BOOTS 3 SIDES 6) ALL WIRES MUST TERMINATE IN APPROVED BOXES 7) SUPPORT ABS PLUMBING HORIZONTAL RUNS AT 4' ON CENTER 8) PEX NOT ALLOWED WITHIN 12" OF RECESSED LIGHTS 9) SUPPORT 4 SWITCH BOXES ON 2 ENDS 10) NAIL PROTECT ALL PLUMBING AND ELECTRIC WITHIN 1 1/4" OF STUD SURFACES
04/21/2002 FRAMING Not ready for Inspection IVRS - Inspection 0000* 1) PLAN CALLS FOR BRICK VENEER