Permit: T01CM03575

Parcel: 12606230B


Addresses:

4011 E 5TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/25/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
07/23/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) ELECTRIC SERVICE PANEL MUST HAVE TWO 8' GROUND RODS AT LEAST 6' APART CONNECTED TO THE SERVICE PANEL WITH A CONTINOUS #4 COPPER CONDUCTOR 2) KITCHEN COUNTER ELECTRIC OUTLETS MUST BE GFCI PROTECTED