Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/01/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/31/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) REMOVE ROOFING FROM 2ND FLOOR FLUE PLUS NUMBERS 1, 2, 3, 6 AND 8 FROM PREVIOUS INSPECTION |
| 10/30/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) DRYER VENT IS 27' LONG WITH 2-90 DEGREE AND 1-45 DEGREE BEND-SHOULD BE 12.5' MAXIMUM 2) NEED H2.5'S ON TRUSS LEDGER IN 3RD CARE 3) STRAP TOP PLATES ACCROSS BEAM AT 2ND/3RD CAR CONNECTION 4) NO WATER PRESSURE 5) CUT FLOOR TRUSS ADJACENT TO BEAM AT STAIRS ? 6) STRAP GAS LINE IN KITCHEN SOFFIT AND AT FIREPLACE 7) FIREPLACE MISSING 2 SCREWS AT TOP 8) TIGHTEN HOLDOWNS 9) FRAME AND PLUMBING PARTIALLED FOR DRYER VENT AND BACKWATER ACCESS 10) GAS TEST OK-10/30 11) STOPPED INSPECTION AFTER 1ST FLOOR |