Permit: T01CM03546

Parcel: 114469370

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/02/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
12/19/2001 MECHANICAL - FINAL Denied IVRS - Inspection 0999*PROVIDE ADEQUATE SLOPE ON CONDENSATE DRAIN ON ROOF. PROVIDE OUTSIDE AIR VENTS ON AC UNITS CONDENSORS ON ROOF NOT FUSED CORRECTLY. CORRECTIONS INSIDE BLDG STILL NO COMPLETE.