Permit: T01CM03536

Parcel: 133095150

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T01CM03536

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/19/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
12/18/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF ELECTRIC, PLUMBING, GAS AND MECHANICAL APPROVAL 2) UNLABELED 7TH BREAKER FROM LEFT TOP 20 AMP ON 14999 WIRE 3) ACCESS TO A/C DISCONNECTS OBSTRUCTED BY UNIT. REQUIRES 30" X 30" WORK SPACE IN FRONT OF DISCONNECTS 4) GFCI OUTLET REQUIRED WITHIN 24" OF RIGHT SIDE OF SINK 5) SMOKE DETECTOR REQUIRED IN BEDFROOM 3 MISSING 6) ELECTRIC OUTLETS IN GARAGE MUST BE AT LEAST 18" ABOVE FLOOR
12/17/2001 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) LOCKED