Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T01CM03536
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/19/2001 | BUILDING - FINAL | Approved | IVRS - Inspection 0000* | |
12/18/2001 | BUILDING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROVIDE PROOF OF ELECTRIC, PLUMBING, GAS AND MECHANICAL APPROVAL 2) UNLABELED 7TH BREAKER FROM LEFT TOP 20 AMP ON 14999 WIRE 3) ACCESS TO A/C DISCONNECTS OBSTRUCTED BY UNIT. REQUIRES 30" X 30" WORK SPACE IN FRONT OF DISCONNECTS 4) GFCI OUTLET REQUIRED WITHIN 24" OF RIGHT SIDE OF SINK 5) SMOKE DETECTOR REQUIRED IN BEDFROOM 3 MISSING 6) ELECTRIC OUTLETS IN GARAGE MUST BE AT LEAST 18" ABOVE FLOOR | |
12/17/2001 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) LOCKED |