Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 10/09/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) REPAIR BEAM SUPPORT AT SOFFIT NEAR FAU VENT 2) NO GAS PRESSURE TEST 3) PARTIAL ON 1025 PENDING #3 SHEARWALL COMPLETION 4) OK-TO INSULATE |
| 09/20/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) ANCHOR BOLTS AT #2 AND #3 SHEARWALLS MUST BE 5/8" DIAMETER 24" ON CENTER (SEE SHEARWALL SCHEDULE) 2) PROVIDE ENGINEER APPROVED FOR ALTERNATE HD AT GREAT ROOM WINDOW 3) SOME HOLDOWNS MISSING 4) #3 SHEARWALLS CALL FOR PLYWOOD BOTH SIDES |
| 09/05/2001 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) LEDGER ATTACHMENT OK |