Permit: T01CM03506

Parcel: 115220500

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/04/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000* OK FINAL SUBJECT TO OTHER INSPECTION.
04/03/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) NM CABLE IS NOT ALLOWED TO BE USED IN A RACEWAY FOR CONNECTION TO A/C UNIT. 2.) PLEASE LABEL A/C UNIT 3.) TIGHTEN AND STRAP SEALTITE AND FITTINGS.
03/21/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*