Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date |
Description |
Inspector |
Results |
Comments |
| 01/31/2002 |
ELECTRIC - UFER |
|
Approved |
IVRS - Inspection 0000*OK 2 GROUND ROD PER SERVICE OK ROUGH ELECT. SERVICE WILL NEED TO BE BONDED TOGETHER 250-58. PLEASE MOVE ONE OF THE PHONE BOXES THAT ARE BACK TO BACK IN THE FIREWALL. |
| 01/28/2002 |
ELECTRIC - UFER |
|
Denied |
1.) PLEASE PROVIDE FHA STRAPS TO PROTECT NM CABLE PASSING THROUGH STUDS 300-4. 2.) A BOX WILL BE NEEDED AT THE EXHAUSTING 373-5 4.) PLEASE INSTALL BOND CLAMPS FOR WATER & GAS. 5.) WE HAVE A BACK TO BACK BOXES IN THE FIRE WALL 300-21. 6.) APPROVED FIRE SEALING METHODS ARE NEEDED AT PENITRATIONS IN THE WALLS AND CEILING AREAS 300-21. 7.) THE NM CABLES ENTERING THE PANEL 8.) UFER'S WERE NOT SEEN BEFORE CONCRETE WAS POURED 2 GROUND ROD WILL BE NEEDED AND BOND BOTH TOGETHER. NOTE: DATA SHOULD BE MOVED OUT FROM UNDER THE PANELS SO AS NOT TO CREATE A WORKING SPACE VIOLATION 110-26 |