Permit: T01CM03506

Parcel: 115220500

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
01/31/2002 ELECTRIC - UFER Approved IVRS - Inspection 0000*OK 2 GROUND ROD PER SERVICE OK ROUGH ELECT. SERVICE WILL NEED TO BE BONDED TOGETHER 250-58. PLEASE MOVE ONE OF THE PHONE BOXES THAT ARE BACK TO BACK IN THE FIREWALL.
01/28/2002 ELECTRIC - UFER Denied 1.) PLEASE PROVIDE FHA STRAPS TO PROTECT NM CABLE PASSING THROUGH STUDS 300-4. 2.) A BOX WILL BE NEEDED AT THE EXHAUSTING 373-5 4.) PLEASE INSTALL BOND CLAMPS FOR WATER & GAS. 5.) WE HAVE A BACK TO BACK BOXES IN THE FIRE WALL 300-21. 6.) APPROVED FIRE SEALING METHODS ARE NEEDED AT PENITRATIONS IN THE WALLS AND CEILING AREAS 300-21. 7.) THE NM CABLES ENTERING THE PANEL 8.) UFER'S WERE NOT SEEN BEFORE CONCRETE WAS POURED 2 GROUND ROD WILL BE NEEDED AND BOND BOTH TOGETHER. NOTE: DATA SHOULD BE MOVED OUT FROM UNDER THE PANELS SO AS NOT TO CREATE A WORKING SPACE VIOLATION 110-26