Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 01/03/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE PROTECT BULB FROM CONTACT OVER SHELF IN LAUNDRY ROOM 2.) A/C DISCONNECTS NEED TO BE LABELED AND TIGHEN LOOSE SEALTITE FITTINGS. 3.) A STRAIN RELIEF CONNECTOR IS REQUIRED AT THE HOOD 373-5. 4.) DO NOT WRAP GROUND WIRE AROUND SCREW MORE THAN 3/4 OF A TURN - NOT MULTIPLE WRAPS.5.) GROUND AND NEUTRALS DOUBLE LUGED AT SERVICE. |