Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/28/2001 |
MECHANICAL - FINAL |
|
Approved |
APPROVED |
| 12/27/2001 |
MECHANICAL - FINAL |
|
Not ready for Inspection |
1.) PKG ROOF TOP HEAT PUMPS LEAVE PROPERLY FUSED! ELECT DATA PLATE NOT MARKED! AUXILARY HEAT STRIP? YES? NO? DONT KNOW? PERMANENTLY MARK AS NECESSARY. 2.) ICE MACHINE CONDENSER REFRIGERENT LINE BUNDLE BLOCKING ACCESS TO CARRIER HT. PUMP. MOVE AS NECESSARY. FINAL WILL COME WHEN DATE PLATE ARE COMPLETED AND PROPER FUSING AT UNITS IS CORRECT. |
| 12/14/2001 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |