Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/14/2001 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 08/09/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*NO CHANGE FROM INSPECTION OF 8/8/01 |
| 08/08/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*THE FLOURESCENT LIGHT FIXTURES (IN THE FRONT ROOM) MUST NOT BE USED FOR THROUGH WIRING. THE ONLY WIRING INTO THE FIXTURE SHOULD BE THE WIRING ENERGIZING THAT FIXTURE. THE FIXTURES ARE NOT APPROVED FOR USE AS A RACEWAY. SOME OF THE 4" SQUARE BOXES ARE OVERFILLED WITH WIRE AND WIRE NUTS.ADD EXTENSION BOXES TO THESE. CORRECT & RECALL. |
| 08/07/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) MOVE M/C OUT OF CHANNEL AND FLEX 2.) LOOSE FITTINGS 3.) OUFER FILL ON CONDUCTORS AT BATHROOM CEILING BOX 4.) NEED EXTENDER RING AT OUTLET IN DRYWALL 5.) SUPPORT FLEX WITHIN 12" OF BOX. |
| 07/30/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) ALL J-BOXES REQUIRED TO HAVE A GROUND TAIL TIED TO ITSOME BOXES ARE SEVERAL NOT 2.) SUPPORT ALL MC CABLE AND FLEX PER CODE 3.) WALL MOUNT FIXTURES NOT ALLOWED TO JUST HAVE A SLOT CUT OUT ON ITS FINISH AND 1/2" CONDUIT RUN INTO SLOT-RACK MUST BE COMPLETE AND INTO BOX 4.) WHAT IS THE SITUATION WITH EXPOSED ROMEX HANGING OUT OR WALL BY BATH ROOM 5.) WILL NEED TO USE LISTED TYPE OF BOXES FO CEILING FANS THE APPEAR TO BE SURFACE TYPE. 6.) SEAL ALL J-BOXES (WHICH HAVE HOLES) 7.) INSTALL ALL PLASTER RING. |