Permit: T01CM03454

Parcel: 21114007C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/16/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/05/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) WE HAVE MULTIPOLE TERMANATIONS UNDER LUGS AT MAIN DISCONNECT (LIGHTING ARRESTOR) 2. PROVIDE REJECTION PNS AT MAIN DISCONNECT. 3.) PLEASE TIGHTEN SEALTITE FITTINGS. 4.) WHERE IS 1/0 COPPER GROUND TO MAIN DISCONNECT AS PER PLANS.5.) PLANS CALL FOR JUNCTION BOX TO BE AT LEAST 10' FROM GAS METER BOX IS LESS THAN 4'