Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/16/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 06/05/2002 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) WE HAVE MULTIPOLE TERMANATIONS UNDER LUGS AT MAIN DISCONNECT (LIGHTING ARRESTOR) 2. PROVIDE REJECTION PNS AT MAIN DISCONNECT. 3.) PLEASE TIGHTEN SEALTITE FITTINGS. 4.) WHERE IS 1/0 COPPER GROUND TO MAIN DISCONNECT AS PER PLANS.5.) PLANS CALL FOR JUNCTION BOX TO BE AT LEAST 10' FROM GAS METER BOX IS LESS THAN 4' |