Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/04/2002 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 03/28/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ALONG WITH INSULATION AND STUCCO CERTIFICATES, A POST TENSION CERTIFICATION IS NEEDED |
| 03/22/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED CERTIFICATES |
| 02/22/2002 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) ROOF INCOMPLETE 2 ELECTRICAL INCOMPLETE 3) ADDRESS NOT POSTED 4) WATER HEATER VENT MUST TERMINATE MINIMUM 2' ABOVE ANY PORTION OF BLDG WITHIN 10' (IRC SEC. M 1804) 5) A/C START UP NOT DONE 6) EXTERIOR GFCI CIRCUIT WON'T TRIP 7) HOSE BIBS REQUIRE ANTI-SIPHON DEVICE 8) ALL PLUMBING FIXTURES MUST BE INSTALLED 9) INSTALL LOG LIGHTER AND FIRE CAULK PENETRATION INTO FIREPLACE |
| 02/20/2002 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |