Permit: T01CM03439

Parcel: 11616180A


Addresses:

1005 N CONTZEN AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/12/2001 FRAMING Approved IVRS - Inspection 0000*
10/11/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) NO PLANS ON SITE 2) GROUT AT TUBS DRY POWDER 3) BATH GFCI MUST BE ON BATHROOM CIRCUITS NOT LAUNDRY 4) ENTRY STEP NOT COMPLETE
10/09/2001 FRAMING Denied IVRS - Inspection 0999*/ 1) FURR OUT MISSING AT ALL WINDOWS 2) BOND GAS LINE 3) ENTRY STOP MISSING 4) BLOCK DEFUSER BOOTS 3 SIDES 5) BACK GROUT/SEAL FLOOR PENETRATION FOR TUB 6) BATH GFCI MUST BE ON CIRCUIT WITH ONLEY BATH AND NO OTHER ROOMS 7) NON READABLE GAS GUAGE-USE GUAGE WITH 1/4" INCREMENTS 8) NO PLAN ON SITE, STOPPED INSPECTION