Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03434
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2002 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 01/31/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NOTES OK HARD LID LIGHTING AND CONDUITS 2ND FLOOR SOFFIT ENTRY AREA BY STAIRS. | |
| 01/30/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*OK BATH ROOMS WALLS, AND HARD LIDS, | |
| 01/23/2002 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*NOTES 1.) OK WALLS 2ND FLOOR CALL FOR CEILING WHEN READY. | |
| 01/22/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) REPLACE MC CABLE IN PARTIAN WALL BY RESTROOM (BROKEN SHEATH.) 2.) MC CABLE NOT SEATED IN CONNECTORS PROPERLY. EXPOSED CONDUCTORS. NEC 110-3 110-12. | |
| 01/18/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1.) RACEWAYS TO BE SECURLY SUPPORTED TO STRUCTURE CANNOT SUPPORT CONDUIT TO CONDUIT, NO GAPS 2.) SEE PRIVIOUS INSPECTION WRITE UP. | |
| 01/17/2002 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245*NOTES 1. PROVIDE LETTER FROM ARCH. AUTHORIZING USE OF MC CABLE. 2.) MC CABLE IF USED MUST BE SUPPORTED PER ART 334. N.E.C. 3.) CONDUIT TO BE SUPPORTED PER NOTES ON ELECTRICAL SPECS SHEET E-O OF PLANS. |