Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T01CM03419
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2002 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
05/07/2002 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection 0999*1.) STRAP FLEX DUCT W/ 1 1/2" HANGER STRAP. 2.) PROVIDE PROPER SLOPE ON CONDENSATE DRAIN LINE. 3.) PROVIDE SECONDARY DRAIN PAN UNDER UNIT. TERMINATE DRAIN, TO A CONSPICUOUS LOCATION. |