Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T01CM03419
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2002 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
05/07/2002 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245*1.) TIE SIEMIC WIRES (2) REQUIRED PER 2 X 4 FIXTURES, ALSO (2) #8 SCREWS REQUIRED TO HOLD FIXTURES TO GRID. 2.) EM OR NIGHT LIGHT CIRCUIT NEEDS TO BE CONNECTED TO WEST END LIGHT FIXTURE SEE PLAN. 3.) FLEXABLE CONDUIT TO BE SUPPORTED PER CODE, DO NOT TIE TO EXISTING CONDUIT. |