Permit: T01CM03418

Parcel: 120052730

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Permit Number - T01CM03418

Inspection Description - BUILDING ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/24/2001 BUILDING ABOVE CEILING Approved IVRS - Inspection 0000*
08/23/2001 BUILDING ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*CEIL GRID WILL NOT PASS INSPECTION SEE UBC 25-2 FOR INSTALLATION REQUIREMENTS -HANGERS REQUIRED 8" FROM WALL ON ALL PERIMETER MAIN RUNNERS & CROSS RUNNERS. CEIL GRID WIRES FOR INTERMEDIATE T-BAR ARE REQUIRED WITHIN 3" OF EACH CORNER OF EACH RECESSED LIGHT FIXTURE.