Permit: T01CM03376

Parcel: 109250330

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/28/2001 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*1.) SOIL WATER TEST IS OK 2.) CONNECTIONS IS OK 3.) OK FOR BACKFILL.
11/27/2001 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*1.) SOIL WATER TEST FOR SOUTH END OF BLDG IS OK 2.) NOTE: PLANS CALLS FOR 4" TRAP ARMS FOR WATER CLOSETS WILL REQUIRE A REVISED & APPROVED DRAWING CHANGING 4" TRAP ARMS TO 3". 3.) OK TO BACKFILL SOUTH END IN BLDG. ONLY 4.) BLDG. SEWERS MUST HAVE SHAPE AND PIPE MUST BE LAID ON FIRM BED. SEC SECTION: 315.4 94 UPC NO BRIDGING ALLOWED. 5.) 4" BLDG. DRAINS ON NORTH END OF BLDG. MUST BE PROPERLY SHAPED. 6.) WATER TEST ON PLBG. SYSTEM ON NORTH END OF BLDG. WAS DOWN. RETEST SYSTEM. DO NOT COVER!
11/26/2001 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*