Permit: T01CM03365

Parcel: 117084100


Addresses:

464 W LA PAZ ST #01

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/19/2002 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) ABS DWV OK 2.) COPPER WATER OK PRESSURE TEST OK 3.) TUBS OK 4.) CLOSET FLANGES OK 5.) GAS PIPE OK PRESSURE TST OK 6.) OK TO COVER WALL.
04/17/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
04/15/2002 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0666*1.) SEPARATE GAS PIPING FROM COPPER PIPING. 2.) REVIEW HANGERS AND SUPPORTS 3.) REMEMBER, WHENEVER YOU CHANGE THE ROUGH- IN BELOW 42", THE NEW, OR REVISED SECTION, MUST BETESTED TO 42". 4.) CLOSET RINGS OK 5.) NOT ALL TUBS FULL OF WATER. 6.) HORIZONTAL ABS TO BE SUPPORTED 4' MAX 7.) COPPER LOCKING MINIMUM SUPPORT 8.) GAS TO BE STRAPPED PER 94 UPC.