Permit: T01CM03352

Parcel: 11207103E


Addresses:

2721 E ALTURAS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/28/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
12/13/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) SQUARE "P" BREAKER NOT ALLOWED IN A CUTLER HAMMER ELECTRIC PANEL 2) LABEL ALL CIRCUITS IN ELECTRIC SERVICE 3) FILL OPEN KNOCKOUTS IN ELECTRICAL SERVICE 4) GFCI OUTLET REQUIRED IN FRONT OF HOUSE 5) #12 WIRE NOT ALLOWED ON 30 AMP CIRCUIT BREAKER 6) 3" WASTE VENT MUST EXTEND 6" ABOVE PARAPET 7) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 8) WATER HEATER VENT MUST BE AT LEAST 5' IN LENGTH AND EXTEND 1 FOOT ABOVE VERTICAL WALL WITHIN 4 FOOT 9) COVER ALL UNUSED LIGHT FIXTURES
12/11/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*