Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/28/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/13/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) SQUARE "P" BREAKER NOT ALLOWED IN A CUTLER HAMMER ELECTRIC PANEL 2) LABEL ALL CIRCUITS IN ELECTRIC SERVICE 3) FILL OPEN KNOCKOUTS IN ELECTRICAL SERVICE 4) GFCI OUTLET REQUIRED IN FRONT OF HOUSE 5) #12 WIRE NOT ALLOWED ON 30 AMP CIRCUIT BREAKER 6) 3" WASTE VENT MUST EXTEND 6" ABOVE PARAPET 7) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 8) WATER HEATER VENT MUST BE AT LEAST 5' IN LENGTH AND EXTEND 1 FOOT ABOVE VERTICAL WALL WITHIN 4 FOOT 9) COVER ALL UNUSED LIGHT FIXTURES |
| 12/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |