Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 09/13/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) INADAQUATE NEUTRAL LIGHT FLOOR AREA 1230 SQUARE FEET. HOUSE HAS 84 SQUARE FEET OF NEUTRAL LIGHT 98 SQUARE FEET REQUIRED-14 SQUARE FEET ADDITIONAL REQUIRED OR PROVIDE AN ENVIORNMENTAL ENGINEERS CERTIFICATIONS OF COMPLIANCES WITH IRC SECTION 303.1 EXCEPTION 1 AND 2 2) PLUMBING NOT COMPLETE 3) OK TO ROCK ALL BUT REPAIR AREAS |
| 08/31/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) LAUNDRY VENT NOT PROPERLY INSTALLED 2) LAV NOT PROPERLY VENTED 3) WEIR OF LAUNDRY "P" TRAP MUST BE BETWEEN 6"+18" OF FLOOR 4) ITEMS 7 AND 8 OF 8/24/01 OPEN |
| 08/24/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*1.) SANITARY "T" FITTINGS ARE NOT ALLOWED IN HORIZONTAL POSITIONS. 2.) LAUNDRY "S" TRAPPED. 3.) LAUNDRY "P" TRAP WEIR CANNOT BE HIGHER THAN 18" ABOVE FLOOR AND 5 AMP PIPE MUST BE LEAST 18" IN LENGTH 4.) KITCHEN DRAIN NOT ALLOWED TO BE HEAL VENTED. 5.) SHOWER REQUIRES 2" DRAIN 6.) GROUND ALL METAL BOXES & MAKE UP ALL GROUNDS. 7.) PROVIDE PLAN REVISION FOR NATURAL LIGHT. 8.) REVISE MECHANICAL PLAN TO AS BUILT. |