Permit: T01CM03350

Parcel: 11502173E


Addresses:

522 E ELM ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/22/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*CORRECTIONS REQUESTED ARE OK.
05/20/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1. PLEASE VERIFY CIELING BOXES ARE LISTED FOR USE WITH A FAN 110-3. 2.) TIGHTEN CONNECTOR AT TOP OF PANEL AND AT METAL BOXES 373-5. 3.) WE HAVE A NM CABLE PASSING THROUGH THE SKYLIGHT OPENING. 4.) PLEASE PROTECT PVC CONDUIT AT BASE PLATE 300-4. 5.) A GAS AND WATER BOND WILL BE REQUIRED 250-104. 6.) A REFRIDERATOR CAN NOT BE ON A LIGHTING CIRCUIT 210-
09/26/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*