Permit: T01CM03326

Parcel: 10309069C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/11/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK FINAL.
10/10/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
10/04/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*WILL NOT GROUP RED LIFT OTHER DOES NOT REACH.
08/05/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*PLEASE VERIFY WHICH UNIT WE HAVE ON JOB. PAPER WORK NOT CLEAR ALSO IS THIS FOR USE IN HAZARDOUS LOCATION AS PER PAPER WORK.
07/22/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*FINISH ITEM #3 VERIFY LISTING FOR EXHAUST FANS.
05/28/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000* 1.) EXTENSION CORDS CAN NOT BE USED AS A PERMANENT WIRING METHOD CORD IS ATTACHED TO BUILDING. 2. FOUNTAIN IS LOCATED IN CLASS 1 DIV 2 LOCATION AND IT IS NOT RATED FOR THIS LOCATION. 3.) PLEASE VERIFY LISTING FOR EXHAUST FANS ON ROOF. 4.) PLEASE VERIFY SUMP PUMP LISTING AS PREVIOUS INSPECTION #4.
05/10/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK TEMP C OF O. 1.) BOND BUSHINGS ARE NEEDED AT A/C DISCONNECTS VOLTAGE IS ABOVE 250V 250- 2.) A/C DISCONNECT NEED TO BE LABELED. 3.) WE AHVE A WORKING SPACE VIOLATION IN FRONT OF A/C DISCONNECTS 4.) SUMP PUMP. IS CORD CONNECTED WITH A 6-8' CORD. PLEASE VERIFY LISTING AND LABLEING. 5.) FINISH OUTLETS IN DATA ROOM & STRAPING CONDUIT. 6.) PLEASE SUPPORT CAN WITH A SUPPORT WIRE AND STRAP M/C CABLE WITHIN 12" CONFERENCE ROOM 7.) WATER HEATERS TO HAVE A DISCONNECTING MEANS. 8.) SUPPORT CONDUITS WITH UNISTRUST STRAPS. 9.) WE HAVE A MISSING JUNCTION BOX COVER.