Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/11/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 10/10/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/04/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*WILL NOT GROUP RED LIFT OTHER DOES NOT REACH. |
| 08/05/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*PLEASE VERIFY WHICH UNIT WE HAVE ON JOB. PAPER WORK NOT CLEAR ALSO IS THIS FOR USE IN HAZARDOUS LOCATION AS PER PAPER WORK. |
| 07/22/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*FINISH ITEM #3 VERIFY LISTING FOR EXHAUST FANS. |
| 05/28/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1.) EXTENSION CORDS CAN NOT BE USED AS A PERMANENT WIRING METHOD CORD IS ATTACHED TO BUILDING. 2. FOUNTAIN IS LOCATED IN CLASS 1 DIV 2 LOCATION AND IT IS NOT RATED FOR THIS LOCATION. 3.) PLEASE VERIFY LISTING FOR EXHAUST FANS ON ROOF. 4.) PLEASE VERIFY SUMP PUMP LISTING AS PREVIOUS INSPECTION #4. |
| 05/10/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*OK TEMP C OF O. 1.) BOND BUSHINGS ARE NEEDED AT A/C DISCONNECTS VOLTAGE IS ABOVE 250V 250- 2.) A/C DISCONNECT NEED TO BE LABELED. 3.) WE AHVE A WORKING SPACE VIOLATION IN FRONT OF A/C DISCONNECTS 4.) SUMP PUMP. IS CORD CONNECTED WITH A 6-8' CORD. PLEASE VERIFY LISTING AND LABLEING. 5.) FINISH OUTLETS IN DATA ROOM & STRAPING CONDUIT. 6.) PLEASE SUPPORT CAN WITH A SUPPORT WIRE AND STRAP M/C CABLE WITHIN 12" CONFERENCE ROOM 7.) WATER HEATERS TO HAVE A DISCONNECTING MEANS. 8.) SUPPORT CONDUITS WITH UNISTRUST STRAPS. 9.) WE HAVE A MISSING JUNCTION BOX COVER. |