Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 07/22/2002 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection 0000* |
| 05/08/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK PANEL LA-2, OK PACKING ON SEALOFFS OK TO POUR RECEIVE LETTER OF TORQUE VALVES. |
| 04/29/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) WE STILL HAVE VDV CABLES NOT SUPPORTED AS PER CODE 300-11. |
| 04/22/2002 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999*2ND FLOOR 1.) WE HAVE WORKING CLEARANCE VIOLATION FOR AN AIR HANDLER ABOVE THE CEILING 110-26. ALSO LABEL THE DISCONNECT SO AS TO IDENTIFY THE UNIT. 2.) RE LOC WIRING TO BE INDEPENDANLY SUPPORTED 300-11. 3.)PLEASE SUPPORT ALL CONDUIT AS PER CODE. 4.) THE 8' FIXTURE NEED TO HAVE SUPPORT WIRES 5.) SUPPORT THE M/C CABLE AS PER CODE. 1ST FLOOR. 1.) PLEASE OPEN TILES FOR REINSPECTION. |
| 04/10/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
1.) PLEASE SUPPORT VDV CABLES ON DEPENDANT WIRE OTHER THAN CIELING WIRES 300-11. 2.) PLEASE SUPPORT RELOCE WIRING METHODS AS PER CODE 3. SUPPORT M/C CABLE AS PER CODE 604,300-11. |
| 03/26/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE PROVIDE REVISED PLANS REFLECTING ADDED LIGHTING AND CIRCUITING. OK STAIR WELL IN SHOP. |
| 03/25/2002 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 03/24/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*1.) SUPPORT CONDUIT AS CODE. |
| 03/18/2002 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection 0000*OK CANAPY BOXES & CONDUIT, OK STAIRWELL EAST CONDUIT & E CANS. |