Permit: T01CM03326

Parcel: 10309069C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/22/2002 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
05/08/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK PANEL LA-2, OK PACKING ON SEALOFFS OK TO POUR RECEIVE LETTER OF TORQUE VALVES.
04/29/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) WE STILL HAVE VDV CABLES NOT SUPPORTED AS PER CODE 300-11.
04/22/2002 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*2ND FLOOR 1.) WE HAVE WORKING CLEARANCE VIOLATION FOR AN AIR HANDLER ABOVE THE CEILING 110-26. ALSO LABEL THE DISCONNECT SO AS TO IDENTIFY THE UNIT. 2.) RE LOC WIRING TO BE INDEPENDANLY SUPPORTED 300-11. 3.)PLEASE SUPPORT ALL CONDUIT AS PER CODE. 4.) THE 8' FIXTURE NEED TO HAVE SUPPORT WIRES 5.) SUPPORT THE M/C CABLE AS PER CODE. 1ST FLOOR. 1.) PLEASE OPEN TILES FOR REINSPECTION.
04/10/2002 ELECTRIC - ABOVE CEILING Partial Approval 1.) PLEASE SUPPORT VDV CABLES ON DEPENDANT WIRE OTHER THAN CIELING WIRES 300-11. 2.) PLEASE SUPPORT RELOCE WIRING METHODS AS PER CODE 3. SUPPORT M/C CABLE AS PER CODE 604,300-11.
03/26/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) PLEASE PROVIDE REVISED PLANS REFLECTING ADDED LIGHTING AND CIRCUITING. OK STAIR WELL IN SHOP.
03/25/2002 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*
03/24/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*1.) SUPPORT CONDUIT AS CODE.
03/18/2002 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*OK CANAPY BOXES & CONDUIT, OK STAIRWELL EAST CONDUIT & E CANS.