Permit: T01CM03326

Parcel: 10309069C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/08/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
05/06/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK PLANS HB,LB,HA,M1,M2, ESA TRANFORM LB,M,LC COOLER STARTERS 1-4 ROOF VENTATOR CONTRACTORS BREAKER TERMANATIONS AT MAIN SWITCH BOARD. 1.) PLEASE TIGHTEN NEUTRAL CONNECTIONS 2.) TRANSFORMER "M" HAS STACKED LUGS. PROVIDE FULL SURFACE CONTRACT. 3.) PLEASE PROVIDE A LETTER VERIFING TORQUE VALVES.
05/01/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) DRINKING FOUNTAIN TO BE LISTED FOR USE IN HAZARDOUS LOCATION OK WALLS AT BAY DOORS NORTH & SOUTH.
03/18/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
02/28/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS UPSTAIRS 2ND FLOOD.
02/14/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WALLS ROOM #118-127
02/11/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK WRITE UP AREA CONDUIT ON BEAMS OK CONDUIT ON BEAMS WASH AREA. OK
WIRING ON BEAMS NO LIGHTS INSTALLED AT THIS TIME.
02/05/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK PORCH CONDUIT FOR LIGHTING COLM. 2-8. METHOD TO INSTALL RELOC SYSTEM FOR LIGHTING MEET THE INTENT OF THE CODE PLEASE FINISH AND CALL FOR INSPECTION.
01/31/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) CONDUIT RUN CAN NOT HAVE MORE THAN 260 INBEND ABOVE WALLS OK WALLS ROOM #103-116 AND SOUTH AND WEST OUTSIDE WALLS.
01/30/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*OK 1" PVC AS MARKED ON PLANS.
01/24/2002 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*OK TO HANG 8' FLOURESCENTS OFF OF 1/2" STEEL PIPE CHAIN SUPPORTS TO BE NO FURTHER THAN 4' FROM FIXTURE JOINTS. OK WIRING AND MAKE UP 14 LIGHT POLES ON THE GROUND.
01/16/2002 ELECTRIC - INTERMEDIATE Partial Approval