Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/07/2001 |
PLUMBING - FINAL |
|
Approved |
1.) VENT TERMINATION ON BLDG. APPROVED. 2.) PROVIDE INSPECTION HISTORY FOR YARDWATER FROM BLDG TO SITE WALL. YARDWATER APPROVED 5/15/01 FM 3.) PLUMBING FINAL OK 4.) OK FOR C OF O. PENDING ANY OTHER INSPECTIONS. |
| 09/04/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.)EXTEND VENTS TO ABOVE PARAPET AND SECURE AND PAINT 2.) YARDWATER LINE HAS NOT BEEN APPROVED. |
| 08/26/2001 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLUMBING FINAL IS COMPLETE 2.) VENT TERMINATION NOT APPROVED 3.) HORIZONTAL VENT TERMINATING AT PARAPET FACE. EXTEND VENT VERTICALLY TO ABOVE PARAPET AND PAINT PER 1.5.313.3 94UPC. |