Permit: T01CM03323

Parcel: 141085320

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T01CM03323

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/12/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/07/2001 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*1.)PLEASE PROVIDE APPROVAL ON LISTING FOR ST CORD FAX 791-4340. OUTSIDE 2.) PLEASE GET ALL EM FIXTURES OMITTED STILL SHOWING SOME ON PLAN.
09/05/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*SEE NOTE BELOW. 1.) EXIT LIGHTS HAVE BEEN DELETED. WILL NEW LOCATIONS BE SELECTED & LITES INSTALLED? HAVE ARCHITECT OF RECORD ADDRESS THIS CHANGE. 2.) EXTERIOR PERIMETER AREA LIGHTING FIXTURES ARE MANUFACTURED FOR POLE MOUNT BUT HAVE BEEN WALL MOUNTED ON SITE. THE FIXTURES ARE WIRED WITH SJ CORD TO A JUNCTION BOX. THE FIXTURE S/B PIPED W/EMT. OR FLEX SYSTEMS.3.) LIGHTING AND POWER FLOOR PLANS MUST BE REVISED AND APPROVED BY CITY. SUBMIT NEW PANEL SCHEDULE TO REFLECT RE-CIRCUITING OF POWER & LITES. THANKS.
09/04/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) OFFICES OK TO OCCUPY. 2.) LABEL ALL PANELS, SWITCHES, AND CIRCUIT BREAKERS.
08/23/2001 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1. WAREHOUSE IS OK. 2. OFFICES INCOMPLETE.