Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T01CM03313
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2001 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection 0000* | |
09/27/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) PLEASE READ NOTE #1 FROM 9/18/01 YOU HAVE NOT PROVIDED AN ISOMETRIC DRAWING WITH DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION. I THINK YOU ARE UNDERSIZED ALSO CHECK FLEX CONNECTOR LENGTH AND SIZE YOU MAY HAVE EXCEEDED ALLOWED LENGTH FOR BTU USE. | |
09/18/2001 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection 0999*1.) PROVIDE APPROVED ISOMETRIC FOR GAS, INCLUDING DEVELOPED LENGTH AND TOTAL BTU OF APPLIANCE 2.)PRESSURE TEST ON 3/4" AT METER GOES TO WHAT? 3.) ONE INCH PIPING TO ANSUL, NOT TESTED. DO NOT TEST THROUGH ANSUL VALVE. |