Permit: T01CM03313

Parcel: 12112024C


Addresses:

5319 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T01CM03313

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
09/27/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) PLEASE READ NOTE #1 FROM 9/18/01 YOU HAVE NOT PROVIDED AN ISOMETRIC DRAWING WITH DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION. I THINK YOU ARE UNDERSIZED ALSO CHECK FLEX CONNECTOR LENGTH AND SIZE YOU MAY HAVE EXCEEDED ALLOWED LENGTH FOR BTU USE.
09/18/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) PROVIDE APPROVED ISOMETRIC FOR GAS, INCLUDING DEVELOPED LENGTH AND TOTAL BTU OF APPLIANCE 2.)PRESSURE TEST ON 3/4" AT METER GOES TO WHAT? 3.) ONE INCH PIPING TO ANSUL, NOT TESTED. DO NOT TEST THROUGH ANSUL VALVE.