Permit: T01CM03294

Parcel: 103175120


Addresses:

3049 N GAIA PL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/08/2002 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK ROUGH.
08/05/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0935*NO WORK PROGRESS STILL NOT READY. THIS IS 4TH INSPECTION CALLED OUT A REFEE HAS BEEN ASSESSED.
07/26/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
07/25/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*
07/21/2002 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000* PLEASE MOVE WRITE UP TO TO1CM03285
07/12/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) OUTLET BOX NEED TO BE FINISHED WIRING 2.) PROTECT CONDUCTORS IN BOXES 370-43. 3.) STRAP NM CABLE WITHIN 12" OF BOXES 336-18. 4.) WE HAVE OVER FILL OF CONDUCTORS IN BOX 370-16 5.) A BOX MAY BE NEEDED AT BATH ROOM? 7.) PLEASE PROTECT DATA CABLE AT STUDS 300-4. 8.) PLEASE PROVIDE REVISED PLANS FOR ELECTRICAL CHANGES FOR THE UNIT. 9.) WE ARE MISSING THE SCREW FOR THE LUG IN THE SUB PANEL PLEASE USE AN ANTIOXIDE COMPOUND FOR ALUMINUM TERMANATIONS 10.) LOOSE FITTINGS AT SUBPANEL.