Permit: T01CM03290

Parcel: 103175070


Addresses:

3039 N GAIA PL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/10/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
03/07/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*
1.) CLEAN UP FLOOR TO ACCESS AIR HANDLER UNDER STAIR WAY.
2.) NEED TO MARK LABEL FAN COILS TO MATCH PROPER CIRCUIT BKR.
3.) AIR HANDLER 1ST FLR. NEEDS TO BE A 30 AMP 2 POLE, NOT 50.
4.) WHAT SIZE FUSES ARE IN 018 HEAT PUMP OUTSIDE SECTION. SIZE IS NOT ON FUSES.