Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/13/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FOR C OF O. APPROVED |
| 12/12/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) INSTALL GFI RECEPTACLES ON ROOF PER PLAN. 2.) INSTALL SINGLE POLE SERVICE SWITCH FOR MUA EVAP. COOLER. |
| 12/10/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/05/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0950*1.) PROVIDE LETTER FROM LICENSED CONTRACTOR ASSUMING RESPONSIBILITY FOR THE ELECTRICAL PLANT. 2.) PROVIDE REVISED "APPROVED" PLAN. 3.) PROVIDE AND INSTALL BACK COVER PLATE FOR ICE MAKER. 4.) PROVIDE SUPPORT FOR 3/8 MC CABLE ALONG WALL WHERE IT EXITS THE CIELING AND ENTERS THE ICE MAKER. 5.) PROVIDE SEPARATION ORINSULATION ON MC CABLE TO KEEP IT FROM CONTACT WITH COPPER REFRIGERATION LINES. 6.) APPLY PERMANENT I.D. TO ELECTRICAL PANELS L1 & 2 ON FRONT OF DOORS. 7.) PROVIDE LADDER TO ACCESS ROOF. 8.) PROVIDE I.D. PLATES ON ROOF MOUNTED A/C POWER SWITCHES. MUST HAVE PANEL AND CIRCUITS SERVING EACH A/C AHU, EXHAUST FAN, MAKE UP AIR, ETC..9.) PROVIDE INFO. IF CIELING LITES MARKED EM/NL REQUIRE BATTERY PACKS FOR BACKUP DURING POWER OUTAGES. |