Permit: T01CM03258

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
03/04/2002 MECHANICAL - FINAL Approved IVRS - Inspection 0000*OK FOR C OF O.
03/01/2002 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*1.) PERMANENTLY LABEL CONDENSING UNITS & FAN COILS 2.) INSTALL GRILLES FOR OUTSIDE AIR W/SCREEN. 3.) FAN COIL S.W. CORNER BLDG. 5 NO ACCESS TO FILTER. 4.) VERTICLE AIR HANDLER S. END BLDG 5 NEEDS
TRAP ON CONDENSATE. 5.) HOOK UP OVERFLOW SENSOR BLDG. 7. N. END.