Permit: T01CM03258

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/27/2002 PLUMBING - FINAL Approved IVRS - Inspection 0000*
02/26/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) NOT READY FOR INSPECTION.
02/25/2002 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) WHEN DID YOU CALL FOR YARD WATE LINE INSPECTION? 2.) ADA RESTROOM DOES NOT MEET ADA REQUIREMENT. 3.) KITCHEN SINK HAS NO C.O. 4.) P & T DRAIN CAN NOT HAVE FLEX LINE PROVIDE UNION IN LINE. 5.) SOIL WATER TEST FOR 4" BLDG. SEWER IS OK 6.) HCS TAP IN STREET IS OK 7.) OK TO BACKFILL TRENCH.