Permit: T01CM03225

Parcel: 11454055A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/07/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) ALL CORRECTION DATED 8/6/01 MADE OK 2.) ALL INTERNAL BACK FLOW DEVICES TESTED OK 3.) FINAL GAS CONNECTION OK 4.) UTILITY SINK CHANGED TO MOP SINK OK 5.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS.
08/06/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) MUST USE L-SWEEPS ON CONTINOUS WASTE WHEN WASTE IS HORIZONTAL TO HORIZONTAL AND VERTICAL TO HORIZONTAL DRAINAGE ON ALL INDIRECT WASTE FOR SINKS. 2.) H.C. WATER CLOSET HANDLES MUST BE ON OPEN SIDE OF RM (ADA SPECS)3.) MUST PROVIDE CABLES FOR QUICK DISSCONNECTS FOR ALL GAS APPLIANCES WITH WHEELS. 4.) MUST SECURE 1/2" CUPPER SUPPLYS FOR ALL SINKS. 5.) PROVIDE TEST & CERT. FOR ALL BACKFLOW PREVENTEES.6.) UTILITY SINK MUST HAVE TRAP ABOVE FLOOR & C.O. OR INDIRECT WASTE. CAN NOT HAVE P-TRAP BELOW FLOOR FOR THIS FIXTURE. 7.) MUST PROVIDE FLOW CONTROL & VENT FOR TRIPLE COMPT SINK.
08/04/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) NOT READY FOR INSPECTIONS.