Permit: T01CM03225

Parcel: 11454055A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/13/2001 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*1.) WATER DISTRIBUTION IN WALL ARE OK 2.) OK TO DRYWALL 3.) ALL CORRECTION HAVE BEEN MADE.
07/12/2001 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*1.) WOOD SHIMS NOT APPROVED STAP. 2) PLUMBERS TAPE NOT APPROVED STRAP 3.) SUPPORT ALL LOOSE VERTICAL PIPING 4.) NO NEW UNDERGROUND PIPING 5.) GAS PIPING OK PRESSURE TEST OK 6.) ISOLAKE COPPER PIPING FROM SIMILAR AND DISSIMILAR METAL 7.) PROVIDE COMBUSTION RELIEF AT WATER HEATER 8.) INSTALL UNION ON TOP RELIEF DRAIN. 9.) SUPPORT EXPANSION TANK.