Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2001 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*1.) WATER DISTRIBUTION IN WALL ARE OK 2.) OK TO DRYWALL 3.) ALL CORRECTION HAVE BEEN MADE. |
| 07/12/2001 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) WOOD SHIMS NOT APPROVED STAP. 2) PLUMBERS TAPE NOT APPROVED STRAP 3.) SUPPORT ALL LOOSE VERTICAL PIPING 4.) NO NEW UNDERGROUND PIPING 5.) GAS PIPING OK PRESSURE TEST OK 6.) ISOLAKE COPPER PIPING FROM SIMILAR AND DISSIMILAR METAL 7.) PROVIDE COMBUSTION RELIEF AT WATER HEATER 8.) INSTALL UNION ON TOP RELIEF DRAIN. 9.) SUPPORT EXPANSION TANK. |