Permit: T01CM03203

Parcel: 10603026A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T01CM03203

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/15/2001 MECHANICAL - INTERMEDIATE Approved
11/13/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) REMOVE PVC FROM R.A. PLENIUM. 2.) TERMINATE COND. DRAIN IN LOW TAIL PIECE.
11/08/2001 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection 0999*2ND TIME 1.) SEAL ALL HOLES IN PLENIUM, SIDES, TOP. 2.) NEED PLASTER GROUND FOR CENTRAL RETURN TO PLENUM (SEE ADJOINING SPACE.)
09/27/2001 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*1.) SUSPENDED FAN COIL RETURN AIR PLENIUM A.) PLENIUM MUST BE COMPLETELY SEALED NO LEAKS. B.)NO COMBUSTIBLES IN A RETURN PLENIUM SUGGEST FRAMING WITH STEEL STUDS. C.) ELECTRICAL ELECT. INSP ADDRESSING PROBLEMS W/ HI VOLTAGE.