Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/15/2001 |
MECHANICAL - INTERMEDIATE |
|
Approved |
|
| 11/13/2001 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) REMOVE PVC FROM R.A. PLENIUM. 2.) TERMINATE COND. DRAIN IN LOW TAIL PIECE. |
| 11/08/2001 |
MECHANICAL - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*2ND TIME 1.) SEAL ALL HOLES IN PLENIUM, SIDES, TOP. 2.) NEED PLASTER GROUND FOR CENTRAL RETURN TO PLENUM (SEE ADJOINING SPACE.) |
| 09/27/2001 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) SUSPENDED FAN COIL RETURN AIR PLENIUM A.) PLENIUM MUST BE COMPLETELY SEALED NO LEAKS. B.)NO COMBUSTIBLES IN A RETURN PLENIUM SUGGEST FRAMING WITH STEEL STUDS. C.) ELECTRICAL ELECT. INSP ADDRESSING PROBLEMS W/ HI VOLTAGE. |