Permit: T01CM03203

Parcel: 10603026A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T01CM03203

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*OK ROUGH.
09/26/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*FINISH PREVIOUS INSPECTION REQUEST CIRCLED ITEMS 2.) NEED DISCONNECTING MEANS FOR SUPENDED FAN COIL AND TO BE ACCESSABLE.
09/24/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*1.) NEED FHA STRAPS 2.) SUPPORT ROMEX AS PER CODE WITHIN 12" OF BOXES 3.) CONDUCTOR FILL HAS BEEN EXCEDED 370-16. 4.) KITCHEN CIRCUITS TO BE 20AMP RATED ALL THE WAY TO PANEL. 5.) SUPPORT CONDUIT AS PER CODE. 6.) SEPERATE GROUNDING AND GROUNDED CONDOCTORS 7.) ONLY ONE WIRE PER TERMAINAL LUG. 8.) LOOSE CONDUIT FITTINGS 9.) SECURE ROMEX CABLE TO BOX 375-3(C) 10.) HOW DID WE ACCESS BACK WEST WALL PLEASE OPEN FOR INSPECTION.
08/29/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*LOCKED NO ADDRESS HAVE APT # ADDED TO PERMIT.
07/06/2001 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*PLEASE TURN PANEL AROUND AND ACCESS WILL BE IN KITCHEN CALL 791-5550 AND HAVE APT #ADDED TO PERMIT.