Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T01CM03203
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*OK ROUGH. | |
| 09/26/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*FINISH PREVIOUS INSPECTION REQUEST CIRCLED ITEMS 2.) NEED DISCONNECTING MEANS FOR SUPENDED FAN COIL AND TO BE ACCESSABLE. | |
| 09/24/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) NEED FHA STRAPS 2.) SUPPORT ROMEX AS PER CODE WITHIN 12" OF BOXES 3.) CONDUCTOR FILL HAS BEEN EXCEDED 370-16. 4.) KITCHEN CIRCUITS TO BE 20AMP RATED ALL THE WAY TO PANEL. 5.) SUPPORT CONDUIT AS PER CODE. 6.) SEPERATE GROUNDING AND GROUNDED CONDOCTORS 7.) ONLY ONE WIRE PER TERMAINAL LUG. 8.) LOOSE CONDUIT FITTINGS 9.) SECURE ROMEX CABLE TO BOX 375-3(C) 10.) HOW DID WE ACCESS BACK WEST WALL PLEASE OPEN FOR INSPECTION. | |
| 08/29/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920*LOCKED NO ADDRESS HAVE APT # ADDED TO PERMIT. | |
| 07/06/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*PLEASE TURN PANEL AROUND AND ACCESS WILL BE IN KITCHEN CALL 791-5550 AND HAVE APT #ADDED TO PERMIT. |