Permit: T01CM03186

Parcel: 136260570


Addresses:

2850 S BECK DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T01CM03186

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
08/29/2001 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) FROM LAST INSPECTION NAIL OFF ALL EXTERIOR SHEATHIN, IF YOU HAVE VERTICAL MEMEBERS ON TRUSSES NAIL OSB ACCORDINGLEY FRONT OSB NOT NAILED OFF ALL SHEAR NAILING IS 16" ON CENTER STUDS, NAIL OFF ALL HORIZONTAL/VERTICAL JOINTS 2) FRONT ARCH, NOTHING TO SUPPORT BOTTOM CHORDS IT GETS STUCCO THEREFORE INSTALL RAT RUN FROM EXTERIOR OF ARCH TO EXTERIOR ENTRY WALL TOTAL OF THREE 3) FROM LAST INSPECTION FRONT GABLE IS NOT NAILED ROOF DECK
08/28/2001 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) NAIL OFF ROOF FRONT GABLE ENTRY 2) NAIL OFF ALL EXTERIOR PLY (VERTICAL) 3) BRACE FRONT ARCH SOFFIT GETS STUCCO NO DRYWALL